Brand Name : ESTEL

Model Number : HE06-40SEH/T

Certification : ISO9001, CE, 3C, FCC, TLC

Place of Origin : Shenzhen, China (Mainland)

MOQ : 1

Price : negotiation

Payment Terms : L/C, D/A, D/P, T/T, Western Union

Supply Ability : 14,000 sets per month

Delivery Time : 7-10 working days

Packaging Details : carton + foam + wooden case

Cooling Method : heat pipe, passive cooling

Protection Level : IP55

Cover Material : galvanized steel

Rated Input Power : 69W

Rated Input Current : 1.45A

Contact Now

DC48V Outdoor Telecom Enclosure Heat Exchanger 400 Watt Top Mounted HE06-40SEH/T

Quick Details:

Place of Origin: Shenzhen, China (Mainland) Rated Heat Exchange Capacity: 40W/K
Brand Name: ESTEL Rated Heating Capacity:300W/500W (optional)
Model: HE06-40SEH/T Input Voltage: DC48V
Product Name: Outdoor Cabinet Heat Exchanger Rated Input Current: 1.45A
Certification: ISO9001, CE, 3C, FCC, TLC Rated Input Power: 69W
Cover Material: galvanized steel Working Temperature: -20°C ~ +55°C
Protection Level: IP55 Noise: 55dB
Installation Mode: top mounted Dimension H×W×D: 176×481.6×543.7mm
Support OEM Cooling Method: heat pipe, passive cooling

Payment & Shipping Terms:

Minimum Order Quantity: 1 set
Price: negotiation
Payment Terms: L/C, D/A, D/P, T/T, Western Union
Supply Ability: 14,000 sets per month
Delivery Time: 7-10 working days
Packaging Details: carton + foam + wooden case

1. Technical Parameters

Model HE06-40SEH/T
Performance Parameters
Rated Voltage (V) DC48V
Rated Current (A) 1.45
Heat Exchange Capacity (W) 400
Heater Power (W) 300
Rated Power (W) 69
Circulation Air Volume (m3/h) 350
Noise (dB(A)) 55
Refrigerant Mixed Liquid
Working Temperature -20°C ~ 55°C
Mechanical Parameters
Installation Mode Top Installed
Height (mm) 176
Width (mm) 481.6
Depth (mm) 543.7
Controller Parameters
Working Voltage (V) DC36~72
Working Temperature and Humidity -20°C ~ +80°C, <90%RH
Temperature Control Accuracy (°C) 0.1
Power Consumption (W) 5
Communication Mode Dry contact,RS485, RS232, GPRS

2. Description

Heat Pipe Heat Exchanger uses refrigerant phase-change heat transfer principle to conduct passive cooling to cabinet equipment compartment. It makes full use of temperature difference between cabinet internal environment and external environment, effectively introduce the external cold air, fast move heat inside the station to the outer environment, to realize cabinet cooling. The energy efficiency ratio of the heat exchanger is above 8~9, with high efficiency and energy saving.

3. Application

The cabinet heat exchanger is widely used for outdoor telecom cabinet, outdoor battery cabinet, outdoor UPS cabinet, outdoor power cabinet, electric cabinet and industry cabinet,etc.

4. Features

(1) Independent energy saving control technology greatly reduces working energy consumption;

(2) LCD control board provides easy installation and maintenance;

(3) Perfect monitoring function, effective monitoring and management on heat exchanger operation;

(4) Integrated design, easy for installation and maintenance;

(5) Protection Level: IP55, anti- corrosion, long service life;

(6) Using DC high efficient fans, greatly lower the product noise, environment friendly;

(7) Good energy saving performance, short investment payback period;

(8) Long service life: more than 10 years, easy maintenance and low cost;

(9) With RS485 remote monitoring interface, fault detection and alarm can be transmitted to monitoring center through controller.

5. Electrical Wiring Diagram

DC48V Outdoor Telecom Enclosure Heat Exchanger 400 Watt Top Mounted HE06-40SEH/T

Wiring Ports:

0V -48V: power supply input (voltage input: DC36 - 65V)

A+ B- SGND: RS485 communication interface

AL1 AL2: general alarm output

F+ F- : auxiliary direct ventilation control output (output voltage: DC48V)

6. System Control Wiring Diagram

DC48V Outdoor Telecom Enclosure Heat Exchanger 400 Watt Top Mounted HE06-40SEH/T

7. Packing and Shipping

DC48V Outdoor Telecom Enclosure Heat Exchanger 400 Watt Top Mounted HE06-40SEH/T

DC48V Outdoor Telecom Enclosure Heat Exchanger 400 Watt Top Mounted HE06-40SEH/T

Our Delivery Agent

The goods can be shipped by sea, by air, by courier, by land, by train, etc.

Besides the following delivery agent, we can also look for the delivery agent with the best price in china if you need us to do for you.

8. Our Contact Information

Mobile Phone: 0086-13752765943

Telephone: 0086-0755 66600941

Email: info@estel.com.cn

lxf.estel@hotmail.com
Skype: fiona.liang10


Product Tags:

cabinet heat exchanger

      

fan heat exchanger

      
Best DC48V Outdoor Telecom Enclosure Heat Exchanger 400 Watt Top Mounted HE06-40SEH/T wholesale

DC48V Outdoor Telecom Enclosure Heat Exchanger 400 Watt Top Mounted HE06-40SEH/T Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Tianjin Estel Electronic Science and Technology Co.,Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0